MINI-PS-100-240AC/24DC/1.5/EX
Signal output DC OK floating
Output description
Continuous current
Output voltage
Status display
Standards
Electrical Equipment for Machinery
Safety transformers for power supply units
Electrical safety (of information technology equipment)
Industrial control equipment
Electronic equipment for use in electrical power installations
SELV
Safe isolation
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
Limitation of mains harmonic currents
Approvals
Granted approvals
Granted approvals for potentially explosive areas
General data
Insulation voltage input/output
Installation position
Degree of protection
Class of protection
MTBF
Housing version
Width
Height
Depth
Weight
Climatic data
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible. relative humidity (operation)
Vibration (operation)
Shock
Pollution degree in acc. with EN 50178
Climatic class
U OUT > 21.5 V: Contact closed
1A
30 V AC/DC
LED green (U out > 21,5 V DC: LED permanently lit)
EN 60204
EN 61558-2-17
EN 60950/VDE 0805 (SELV)
UL/C-UL recognized UL 60950
UL/C-UL Listed UL 508
EN 50178/VDE 0160 (PELV)
EN 60950 (SELV) and EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-101
EN 61000-3-2
u
U / ATEX X II 3G Ex nAC IIC T4 X
3 kV (routine test)
4 kV (type test)
On horizontal DIN rail NS 35 in acc. with EN 60715
IP20
II (in an enclosed control cabinet)
> 500 000 h in acc. with IEC 61709 (SN 29500)
Polyamide PA, color: green
35 mm
99 mm
95 mm
0.25 kg
-25 °C ... 70 °C (> 60°C derating)
-40 °C ... 85 °C
95 % (at 25°C, no condensation)
< 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
30g in all directions in acc. with IEC 60068-2-27
2
3K3 (in acc. with EN 60721)
103074_00_en
PHOENIX CONTACT
3